Can you put a smart switch on a range hood?

Only on a hood built to run from a wall switch, such as the Broan rocker hoods with ADA wiring sheets. Then check the fan's amps against the switch's fan rating. A hood with electronic buttons can wake up in standby when power returns, so the wall switch turns it on and the fan still sits still.

Two answers circulate, and both skip the hood's controls#

Ask this on a forum and you get two replies.

The first says a hood is just a fan and a light, so any smart switch works. The second says no, because Lutron's spec sheet rules out kitchen exhaust fans.

The second answer misreads Lutron. The line it quotes is real. Lutron's Caseta spec submittal (369987m) has a footnote that says "Not for use with fans that have integrated fan speed and / or light control modules, DC motor fans, fans with remote controls, bathroom or kitchen exhaust type fans." But that footnote is marked on one product, the PD-FSQN fan speed control. It is not marked on the Caseta on/off switches, the PD-5ANS, PD-6ANS and PD-5WS-DV. Each of those has its own "Fan" row in the same table.

The first answer is closer, but it misses the part that decides it. What matters is not the fan. It is how the hood's own controls behave when power is cut and comes back.

The terms the answer turns on#

A smart switch does one thing to a hood. It cuts the 120 V supply or restores it, the same as a plain wall switch. So the question is whether that one action is enough to run your hood.

Which hoods are built for a wall switch#

Broan answers this for its own hoods, model series by series. Its help page says to open the hood's product page and look for "ADA Wiring Instructions" under Resources. Each sheet names the series it covers. Broan says the hoods meet the ADA when the controls sit "15” to 48” above the floor" and do not need "reaching over a cooking appliance."

There are three kinds of sheet, and they lead to three different answers.

Rocker hoods, high voltage. Broan's sheet 99045859A covers single-blower hoods with an elongated rocker control: the Broan BKSH and CRSH series, the NuTone NKSH and the Venmar Bistro VBLSH. A second sheet, 99045858A, covers rocker hoods in the Broan BCS3, BCSD, BCSEK, BKSA, BKSF, BNSC, BQSEN, BQSJ, CLSC, CRSA and CRSF series, plus NuTone AHSA, AVSF, NCS3, NCSEK, NKSA and NQSEN. Both sheets say the same thing about parts: "Use standard switches that are rated 120 VCA, 15 A. Only use wires suitable for at least 90oC (194oF)."

The wiring is a 14/3 cable from a two-rocker wall switch to the hood. One rocker runs the motor and one runs the lights. Inside the hood, the installer cuts the black wire that feeds the hood's motor and light switches. The red wire from the wall motor switch then feeds the hood's motor switch. So the wall switch sits in front of the hood's own rocker. It does not replace it.

Two-speed hoods with the HAWSK3 kit. Broan's HAWSK3 kit is for "a two-speed mechanical control and one level lighting range hood." It holds a "Wall switch, 3-way, 120 V, 15 A" for speed and a "Wall switch, dual single pole, 120 V, 15 A" for motor on and off and the light. Its spec sheet lists the hood series it fits, among them PM300SS, BBN1, BCSEK1, BQSEN1, CLSC2, CRSF1 and the BU2 and 40000 families. A smart on/off switch can do the job of the motor on/off switch. It cannot do the 3-way speed switch, so the speed stays wherever that switch is set.

Electronic hoods, low voltage. Broan's sheet 99045883D is for hoods with electronic controls. These include the Broan BCDA1, BKDD1, BKDF1 and BQDD1, the Broan Elite ALT2 and TEN2, and the NuTone AHDA1 and NKDF1, among others. Here the wall control is not a power switch at all. A thin ADA cable plugs into "the 6-pin connector on control board". At the wall it goes to a "momentary normally open contact switch", meaning a button that closes only while pressed. Each press on the motor button steps the blower: low, then medium, then high, then off.

A smart wall switch is not that part. It switches 120 V and holds a position. Broan names no smart device for the low-voltage input, so this page does not suggest one.

If your hood is not on any sheet, Broan's advice on moving controls is short: "Altering the product voids manufacturer's warranty. Check for models that already offer remote switch options."

Why an electronic hood can stay off#

A hood with electronic buttons is where a smart switch stops working the way people expect.

Cosmo's KS series manual (COS-KS6U30 and COS-KS6U36) puts it plainly: "Once the range hood is connected and turned on, the range hood will enter standby mode. You can press the power button to start the motor or the light button to turn on the light."

So a smart switch or smart plug on a hood like this gives you half the job. Off works, because cutting the power stops everything. On does not. Restoring power wakes the board into standby, and the blower waits for a finger on the hood's power button. A schedule, a scene or a voice command that turns the switch on gets a hood that sits there doing nothing.

The forum projects that work copy the hood's own controls instead of cutting its power. In a 2017 SmartThings thread, an owner with a high/low/off hood used a Z-Wave double relay plus a second relay to mirror its switch positions. On the openHAB forum in 2025, an owner with a ceiling hood used an RF bridge that "could learn all RF-codes of the extractor." A smart plug on a plug-in hood meets the same standby wall, and smart plugs and energy monitoring covers why motors are hard on any relay.

What hoods draw, and what switches allow#

Once you know the hood takes a wall switch, the second check is amps. The number to compare is the switch's fan or motor rating, never its 15 A headline.

HoodControlsPublished drawWall switch wiring published
Broan Sahale BKSH130 (30 in)2-speed rocker120 V, 1.4 AYes, sheet 99045859A
Cosmo COS-KS6U30Electronic buttons, remote receiver2 x 238 W motor input at 110 V, about 4.3 A by arithmeticNone in the manual read

Sources: Broan BKSH1 series spec sheet; Cosmo KS series manual.

The Cosmo figure is watts divided by volts, 476 W over 110 V. A motor draws a little more current than that, so 4.3 A is a floor, not a ceiling.

Smart switchRating for fans or motorsThat rating in ampsNeutral
Inovelli fan switch (White Series, per the thread)2.5 A, "not designed for a lighting load"2.5 ANot covered in the thread read
Lutron Caseta PD-5WS-DVFan 3 A, 0.4 A minimum3 ANot required
Lutron Caseta PD-5ANSFan 3 A, 0.1 A minimum3 ARequired
Lutron Caseta PD-6ANSFan 3.6 A, 0.1 A minimum3.6 ARequired
Kasa HS2001/6 HP motor4.4 ARequired
Leviton D315S1/3 HP7.2 ARequired
Leviton D215S (discontinued)3/4 HP motor13.8 ANot covered on the page read

Sources: Lutron spec submittal 369987m; Inovelli staff reply in the community thread; Kasa HS200 page; Leviton D315S and D215S pages. Horsepower converted to amps at 115 V with NEC Table 430.248 (2020).

The Inovelli figure comes from Inovelli staff, asked about a kitchen range hood in June 2025. The reply gave the switch's limit as "Maximum Load (Amps): 2.5 Amps (No more than 2 fans on the switch)" and warned that "the fan switches are not designed for a lighting load." For a hood whose light and fan are on separate wires, the same reply suggested looking at "a relay (Matter, Zigbee, or Z-Wave)" with automations, the pattern a smart switch for a whole house fan uses for two speeds.

Leviton lists "exhaust fans" among the loads for both its D315S and D215S. Lutron's PD-5WS-DV runs without a neutral, but it needs at least 0.4 A to work, a limit explained in no-neutral smart switch minimum load. A 1.4 A hood clears it.

Worked through: a Broan BKSH130 on a Lutron PD-6ANS#

Take one case and walk it through the published figures. Suppose a kitchen has a Broan BKSH130 rocker hood, and the owner wants a wall switch they can put on a schedule.

  1. Does the hood take a wall switch? Yes. The BKSH series is on Broan's sheet 99045859A, and the spec sheet lists the BKSH130 as "ADA Capable: yes."
  2. Does the switch fit the rating? The hood draws 1.4 A at 120 V. The PD-6ANS fan rating is 3.6 A. That leaves room, and the 0.1 A minimum is no issue.
  3. What does the switch control? Following Broan's wiring, the wall switch feeds the hood's own motor rocker. So the hood rocker is left on, at the speed the owner wants. The wall switch then starts and stops the blower at that speed.
  4. What about the light? The second rocker in Broan's wiring runs the lights. A second smart switch could go there, or the light can stay on a plain switch.

Now swap in a Cosmo COS-KS6U30. It fails twice. Its draw of at least 4.3 A is over every Lutron and Inovelli fan rating in the table, and level with the HS200's 4.4 A. And even if a bigger switch fit, its manual says power on brings it to standby. The switch would turn the hood on, and the blower would not start.

Now swap in a Broan hood from the low-voltage sheet, such as a BKDD1. The amps are not the question. Broan's wall control for that hood is a momentary button on a low-voltage cable, and a smart wall switch is a different kind of device.

Which route, by hood#

Your hoodWhat can go on the wallWhy
Rocker hood on Broan sheet 99045859A or 99045858AA smart on/off switch whose fan rating covers the hood's amps, with the hood rocker left onBroan wires a standard 120 V, 15 A switch in front of the hood's motor switch
Two-speed mechanical hood on the HAWSK3 listA smart on/off switch in place of the kit's motor on/off switch onlySpeed is set by the kit's 3-way switch, which an on/off switch does not replace
Electronic hood on Broan sheet 99045883DBroan's momentary contact switch on its ADA cable, not a smart switchThe hood takes a button on a low-voltage cable, not a power switch
Electronic hood whose manual says it powers up in standby, such as the Cosmo KS seriesNot a smart switch or plug, if you want it to turn onCosmo's manual says power on brings the hood to standby
Any hood, controls moved without the maker's sheetNothingBroan says altering the product voids the warranty
Hood light on an Inovelli fan switchNoInovelli staff say the fan switch is not designed for a lighting load

Before you wire anything#

Where this page stops#

This page reads Broan-NuTone's own ADA sheets, the HAWSK3 kit sheet and one Broan spec sheet, plus one Cosmo manual for a hood with electronic buttons. Other makers' hoods were not read. An electronic hood from another brand may behave differently on power up, and its own manual is the one to trust. Zephyr's help center could not be fetched, so the page makes no claim about Zephyr hoods. The switch ratings are as their makers published them in November 2026, and the Inovelli figure comes from a staff reply, not a manual. The page does not cover makeup air, duct size or gas cooktop venting, and nothing here says an automated hood is a safe stand-in for turning it on yourself while cooking. Automation design covers keeping a manual switch that always works. Broan's sheets say the work "must be done by qualified person(s) in accordance with all applicable codes and standards." In the United States that means the National Electrical Code as your town adopts it, and many places require a permit or a licensed electrician. A renter should leave the hood wiring alone; a smart home for renters covers what needs no wiring. Nothing on this page is an installation instruction.

Can I put a smart switch on my range hood?

Only if the hood is built to run from a wall switch, and only if the switch's fan rating covers the hood. Broan publishes wall switch wiring for its rocker hoods, such as the BKSH series, with standard 120 V, 15 A switches. A 1.4 A BKSH130 fits under Lutron's 3.6 A PD-6ANS fan rating.

Does Lutron Caseta work with a range hood?

Lutron's "bathroom or kitchen exhaust type fans" exclusion is a footnote on the PD-FSQN fan speed control. The Caseta on/off switches have their own fan ratings: 3 A for the PD-5ANS and PD-5WS-DV, and 3.6 A for the PD-6ANS. Whether the hood can run from any wall switch is a separate question, answered by the hood's maker.

Why doesn't my range hood turn on with a smart switch?

It probably has electronic controls. Cosmo's KS series manual says that once the hood is connected and turned on, it "will enter standby mode," and you then press the power button to start the motor. Restoring power wakes the board but does not start the fan.

Can I use a smart plug on a range hood?

The same rule applies to a plug-in hood. A plug cuts and restores power the way a wall switch does. A hood that comes back in standby, as Cosmo's KS series does, lets the plug turn it off but not start it. Check the plug's motor rating against the hood's amps too.

How many amps does a range hood draw?

It varies by blower. Broan lists its 30 in BKSH130 at 1.4 A on 120 V. Cosmo's COS-KS6U30 has two motors at 238 W each, about 4.3 A or a little more at 110 V. Read your hood's spec sheet or label.