Can a Nest or ecobee smart thermostat control a pellet stove?
Yes, but not wired like a furnace. A pellet stove reads its thermostat as a plain switch across two terminals, and it makes its own small signal there. A Nest or ecobee needs 24 V that the stove does not give it, so you add a transformer for the thermostat and keep the stove's two wires apart from it.
Two answers circulate, and both are half right#
Ask this on a hearth forum and you get two replies.
The first says it cannot be done. "Pellet stoves are millivolt systems and a nest needs 24 volts to operate," one Hearth.com member wrote in a 2020 thread on a Harman P68. That is true of the thermostat's power. The stove does not supply the 24 V a Nest or ecobee runs on.
The second says wire it to R and W like any furnace. An Englander owner was told exactly that: "R and w.... For a two wire system." That works for a thermostat that needs no power. A Wi-Fi thermostat wired that way has nothing to run on.
The right answer joins them. The stove is happy with any switch that closes its loop. The thermostat needs its own power. Keep the two circuits apart and both are satisfied.
The terms the answer rests on#
- Call for heat. The thermostat closing a contact to tell the heater to run. Enviro's manual puts it plainly: "the thermostat calls for heat (contacts are closed)".
- Dry contact. A switch that adds no power of its own. It only connects two wires. The stove sends its own signal through it and reads whether the loop is open or closed. That is how a pellet stove reads a thermostat.
- Millivolt. A tiny voltage, thousandths of a volt. Harman asks for a thermostat that is "millivolt compatible" and "low current", with gold contacts, because the thermostat sits in the loop of the stove's room probe.
- R, Rh, Rc, W and C. The thermostat terminals. R is the hot side of the power. Rh is R for heating, Rc is R for cooling. W is the heat call. C, the common wire, is the other side of the transformer and gives the thermostat steady power.
- Isolation relay. A switch worked by a small 24 V coil. The thermostat drives the coil, and the relay's own contact closes the stove's loop. The two circuits never touch.
What each stove maker asks of the thermostat#
Every stove manual read here wants two wires and a switch. What they say about the signal differs.
Harman. A 2007 technical bulletin covers "all Harman Pellet Stoves". It says the thermostat must be "1) Millivolt compatible 2) Gold Contacts 3) Low Voltage 4) Low current". It is wired "in series with the room sensing probe using the Rh and W terminals". If there is a jumper between Rh and Rc, "it must be removed". Harman asks for "minimum 2- conductor 24 gauge twisted pair wire". The two thermostats it names are Honeywell's RTH230B and RTH6300B.
The Harman setup is unusual. The stove keeps its own room probe, and the wall thermostat only breaks one leg of it. While you are home, Harman says to set the thermostat to its maximum (82°F, say), so the probe controls the room. When you are out, it is a setback (60°F, say). When the thermostat opens, an auto-ignite stove in auto mode shuts down and shows a "4-blink" status, then relights when it closes. A manual-ignite stove drops to a minimum burn instead.
Quadra-Fire Castile. The insert's owner's manual says "A 12 volt AC thermostat is required to operate this pellet appliance." The thermostat that ships with it has a heat anticipator, and "The current rating is .05 amps." The wires go on "The center 2 screws" of a four-screw block left of the power cord. When the room is warm enough, "the appliance will shut down." On each start it burns on High for about 4 minutes before settling at its set rate.
Englander 25-CBEP and 25-PAH. Both manuals have the same steps. Find block J18 on the control board. It has a factory jumper that "bypasses the thermostat and should be saved". Remove it and "Insert the two thermostat wires in place of the 'jumper'." Englander does not state the voltage on J18. The stove ships in "On/Off mode", which starts and stops it like a furnace. A "High/Low mode" instead drops to the low heat range when the call ends. The manual warns: "Using a thermostat in On/Off mode may shorten the life of your stove's igniter."
Enviro Empress. The control board has a mode switch. In High/Low, the stove drops to LOW when the contacts open. In Auto/Off, it drops to LOW "for 30 minutes". If the contacts close inside that time it carries on. If not, it begins its shutdown.
PelPro and Glow Boy (Dansons). A thermostat module plugs into the board. The two thermostat wires go on a block marked "T'STAT INPUT", "1 per terminal". The control offers a High/Low and an On/Off thermostat cycle. No voltage is stated.
So two makers name the signal, 12 V AC on the Castile and millivolt on Harman, and three say only "two wires". None of the five gives the thermostat a C terminal to run on.
Route 1: a separate transformer, with Rh and Rc kept apart#
This route uses the fact that some thermostats have two R terminals. Google's jumper wire page says an R wire "can go into a Nest Learning Thermostat's Rc or Rh connector." It adds that if "you have separate heating and air conditioning systems", you can put the Rc wire in Rc and the Rh wire in Rh. Nest Learning Thermostats use "an internal jumper between the Rh and Rc connectors", used only "if your system needs it."
The pellet stove wiring borrows that two-supply layout:
- A 120 V to 24 V AC transformer powers the thermostat: one side to Rc, the other to C.
- The stove's two thermostat wires go to Rh and W (W1 on most smart thermostats).
- No jumper between Rh and Rc. Harman says so for its stoves, and the reason holds for all of them: a jumper would put your transformer's 24 V onto the stove's thermostat input.
- Set the thermostat up as heat only.
When the thermostat calls for heat, it connects Rh to W. To the stove, that is the old thermostat's switch closing. The transformer only keeps the screen and Wi-Fi alive.
A documented case on Hearth.com, posted in January 2019, used this layout with a Quadra-Fire CB1200i and an ecobee3 lite. The owner used an ELK-TRG2440 transformer, "24 volt AC, 40 VA". Its two outer terminals went to the ecobee's Rc and C. The stove's control wires went to Rh and W1, and the owner wrote that "it did not matter which one was wired to Rh and W1." The ecobee was set up as a boiler. That is one owner's report, not ecobee's instruction.
The power budget is easy. Google lists 20 to 30 V AC for every Nest thermostat. It gives the 4th gen Learning Thermostat's draw as 4 VA at startup and 2 VA in standby, so a 40 VA transformer has plenty to spare. Transformer sizing is the same sum as for a video doorbell transformer.
This route needs a thermostat with separate Rh and Rc terminals. Google says "The Nest Thermostat E only has an R connector". A thermostat like that cannot keep the two circuits apart, so it needs Route 2.
Route 2: an isolation relay#
The relay route works with any 24 V thermostat, including single-R models. It is the same layout the millivolt fireplace page draws:
- A 24 V transformer powers the thermostat on R and C.
- The thermostat's W drives the relay coil. The coil's other side goes to C.
- The relay's normally open contact takes the stove's two thermostat wires.
The stove's loop now touches only the relay contact, never the thermostat.
This is the route the Harman P68 owner described in 2020: "I used a 24v transformer and fan relay... wire the room temp sensor through the relay and the Nest is powered via the transformer and when it 'calls' it closes the relay." It is also the shape of the Home Assistant answer for a Heatilator stove: a "dry contact relay and temp sensor", run as a generic thermostat.
On a Harman, apply the bulletin's list to the relay too. The relay contact is what now sits in series with the room probe, so it is the part that has to be gold, low voltage and low current. A relay sold for line-voltage loads does not say it meets that. The pump start relay page shows the opposite case, where the relay switches a far bigger load than its coil.
Which route, by stove#
Each row below restates a ruling from the sections above.
| Stove | Where the thermostat lands | What the maker asks | Route |
|---|---|---|---|
| Harman (all pellet stoves, per the bulletin) | Rh and W, in series with the room probe | "Millivolt compatible", gold contacts, low voltage, low current; remove the Rh to Rc jumper | Relay, with a contact that meets Harman's list |
| Quadra-Fire Castile | Center two screws of the terminal block | "A 12 volt AC thermostat", 0.05 A | Split Rh and Rc on a thermostat that has both, or relay |
| Englander 25-CBEP, 25-PAH | Block J18, in place of the factory jumper | Two wires; no voltage stated | Relay, since the signal is not stated |
| Enviro Empress | Board thermostat input | Contacts closed means call | Relay, since the signal is not stated |
| PelPro, Glow Boy | "T'STAT INPUT" on the thermostat module | Two wires; no voltage stated | Relay, since the signal is not stated |
| Any stove, with a single-R thermostat such as Nest Thermostat E | As the stove's manual says | As above | Relay |
The rule behind the table: split Rh and Rc only where the maker names a signal, as Quadra-Fire does. Where the manual is silent, a relay contact closes the loop just as the old thermostat did.
Worked through: a Castile insert and an ecobee#
Here is one case, walked through the published figures. Take a Quadra-Fire Castile insert with the thermostat it shipped with, and an owner who wants an ecobee in its place.
The signal. The manual says the stove wants "a 12 volt AC thermostat" at 0.05 A. That is a small, named signal, so Route 1 fits. The ecobee's Rh to W1 switch will carry the stove's 12 V AC, and the 24 V supply stays on Rc.
The power. A 24 V AC, 40 VA transformer, like the ELK-TRG2440 in the Hearth.com post, plugs into an outlet near the stove. Its two outer terminals go to Rc and C on the ecobee. Run two-conductor thermostat wire from it to the wall.
The stove wires. The old thermostat's two wires stay on the center two screws at the stove. At the wall, move them from the old thermostat to Rh and W1. Check that nothing joins Rh to Rc.
The setup. Choose heat only, with a boiler as the equipment type, as the CB1200i owner did.
The cycling. Each call starts the Castile on High for about 4 minutes. Short calls would spend much of each run in that startup. The CB1200i owner set the Heat Differential Temperature to 3.0°F, the most the app allowed then, and the Heat Minimum On Time to 15 minutes. Those are one owner's numbers, not Quadra-Fire's. They show the direction: wide and slow.
The outcome. With those settings, the room falls 3°F below the setpoint before the ecobee closes Rh to W1. The Castile then lights and runs at least 15 minutes.
The same walkthrough on a Harman ends differently. Harman's bulletin wants the thermostat in the probe loop with gold, low current contacts, and nothing read here says a Nest's or ecobee's W output is one. So the Harman version adds a relay, and the smart thermostat sets the back-off temperature while the stove's own probe holds the room.
Slow the cycling down#
A pellet stove pays for every start. An auto-ignite stove runs its igniter each time, which is why Englander warns about igniter life. The Castile burns on High for about 4 minutes before settling, and its convection blower keeps running after the call ends "until the appliance has cooled down."
- Use High/Low mode where the stove has it. Englander, Enviro and PelPro all offer a High/Low thermostat mode. Englander and Enviro say it drops the stove to low instead of shutting it off. Englander's warning about igniter life is about On/Off mode only.
- Widen the differential and set a minimum on time. The ecobee case above used 3.0°F and 15 minutes.
- Mount the thermostat away from the stove's air. Quadra-Fire says not "in direct line with the appliance convection air". Englander says near the stove "in a central location", because a thermostat in a distant room can let the stove overheat its own room.
Once the stove is on a smart thermostat, schedules and presence rules become possible. Before you rely on them, check what still works when the internet goes down and whether your platform runs schedules locally, as local versus cloud control explains.
Where this page stops#
This page rests on six stove documents and two Google pages, read in November 2026, plus four owner threads. Harman's bulletin dates from 2007 and the Castile manual from 2009, and newer stoves may differ; the P68 owner was "not so sure" the relay method fits Harman's 52i-TC. Newer Quadra-Fire manuals and Castle and Comfortbilt manuals were not read, so the page makes no claim about them. Neither Google nor ecobee publishes pellet stove wiring in anything read here, and nothing read says whether either supports their thermostat in this layout. Treat both routes as wiring you take on yourself. The 120 V side and the stove's warranty are your own to check, and a pellet stove belongs in a room with a working smoke and CO alarm, whatever thermostat runs it. Gas fireplaces are a different circuit, covered in smart thermostats for millivolt fireplaces. Electric fireplaces are a plug question, in electric fireplaces on a smart plug. The wider picture is in smart thermostats and the C wire and which smart thermostats work without a C wire.
Can I use a Nest thermostat with a pellet stove?
Yes, with a 24 V AC transformer for the Nest. On a Nest Learning Thermostat, put the transformer on Rc and C and the stove's two wires on Rh and W1, with no jumper. A Nest Thermostat E has a single R connector, so it needs an isolation relay between it and the stove.
How do I wire an ecobee to a pellet stove?
One documented case, a Quadra-Fire CB1200i with an ecobee3 lite, used a 24 V AC 40 VA transformer on Rc and C and the stove's wires on Rh and W1, set up as a boiler. ecobee does not publish this wiring, so it rests on that owner's report.
What voltage is on a pellet stove's thermostat wires?
It depends on the stove. Quadra-Fire's Castile asks for "a 12 volt AC thermostat" at 0.05 A. Harman asks for a "millivolt compatible", low current thermostat. Englander, Enviro and PelPro manuals do not state a voltage.
Will a smart thermostat wear out my pellet stove's igniter?
It can if it cycles the stove on and off often. Englander warns that On/Off mode "may shorten the life of your stove's igniter." Use High/Low mode where the stove offers it, and set a wide differential and a long minimum on time.
Can I control a pellet stove with Home Assistant?
Yes, by closing the stove's thermostat loop with a dry contact relay and using a temperature sensor, set up as a generic thermostat. A Home Assistant community thread on a Heatilator stove settled on exactly that. See Home Assistant for the platform itself.
Primary sources
Specification and vendor documentation we checked while writing this page. Where a claim depends on firmware behaviour rather than a published spec, the page says so inline.
- Harman, technical bulletin "Adding a programmable set back thermostat for all Harman Pellet Stoves" (March 2007)
- Quadra-Fire, Castile pellet insert owner's manual 250-7251G (August 2009)
- England's Stove Works, Englander 25-CBEP installation and operation manual
- England's Stove Works, Englander 25-PAH, 50-SHPAH and 55-TRPAH owner's manual
- Enviro, Empress control board operating instructions (C-11825)
- Dansons (PelPro and Glow Boy), thermostat installation instructions
- Google Nest Help, Learn about thermostat jumper wires
- Google Nest Help, Nest thermostat technical specifications
- Hearth.com forum, Quadra-Fire CB1200i with ecobee3 lite smart thermostat (January 2019)
- Hearth.com forum, Nest thermostat and Harman P68 (2020 to 2023)
- Hearth.com forum, Englander 25 PDVC hooking up thermostat
- Home Assistant community, thermostat for pellet stove