Can a smart thermostat control a 240V garage heater?

Yes, but never by carrying the heater's power. A Nest or ecobee switches a 24 V signal. Either the heater has 24 V thermostat terminals, or a relay sized to the heater's amps does the switching while the fan circuit stays live.

Two answers circulate, and each leaves out a number#

The first answer says a Nest or ecobee cannot run a 240 V heater, so buy a line-voltage smart thermostat. That is right for baseboard heat, as which smart thermostats work with electric baseboard heaters shows. It goes wrong on a garage unit heater for two reasons. The line-voltage models there top out at 3,000 to 4,000 W at 240 V, and many garage heaters are bigger. And a thermostat in the supply line cuts power to the fan, which the heater makers below forbid.

The second answer says put in a relay or a contactor and let the smart thermostat drive it. That is the right idea, and it is how the HeatingHelp regulars describe it. "Just pure plain and simple open or close a switch," Jamie Hall wrote in a 2021 thread on a Nest and a 240 V heater. "Be especially cautious about electronic (typically Triac) switches." What the short version skips is the amp rating, which circuit the relay breaks, and how low the thermostat will let you set the heat.

That last one is the surprise for many garage owners. A Garage Journal member in Illinois wanted a heater that came on at 35°F and off at 40°F, just to keep the garage above freezing. Neither the Nest nor the ecobee read here takes 35°F as a normal setpoint.

The terms the answer rests on#

Route 1: a heater with 24 V thermostat terminals#

Some garage heaters are built for a remote thermostat. King's KB ECO2S+ series spec sheet lists "Built-In provision for optional 24V remote thermostat" and "Compatible with NEST / any 24V WIFI Stat." King's installation manual says "All thermostat signals for ECO2S+ and PlatinumX models are 24Vac controlled." It adds that "Any thermostat that can pass a low voltage 24Vac signal can be used."

King's manual gives the wiring terminal by terminal. For an ecobee, R goes to R ("POWER (24VAC)"), C to C, W1 to stage 1 heat, W2 to stage 2 heat and G to fan only. For a Nest Learning Thermostat, Rh goes to R, with W1, W2, G and C as for the ecobee. King's note says "The C wire keeps the Nest charged." Y1, Y2, O/B and Rc are "NOT USED on KING HEATERS."

The heater supplies the 24 V, so there is no transformer to add and no relay to size. Two DIP switches on the display select remote or local control. A third switch on the board picks a single-stage or two-stage remote thermostat. If the display shows "L5" with a remote thermostat, King says to set DIP switch 1 to ON.

This route works at any heater size, because the thermostat only ever sees 24 V. King lists the ECO2S+ from 4 kW to 15 kW. The 7.5 kW KB2407 draws 31.2 A at 240 V, and the Nest wiring is the same as on the 4 kW model.

Route 2: a relay sized to the heater's amps#

Most garage heaters ship with a dial thermostat built in and no 24 V terminals. Fahrenheat's FUH series is a common one. Its built-in thermostat is single pole, with a range of 45°F to 135°F. To put a Nest or ecobee on a heater like this, a relay does the switching.

Size the relay to the heater's amps. Amps are watts divided by volts. Fahrenheat's spec sheet does the sums for each model:

Heater at 240 VWattsAmps (Fahrenheat or King figure)Resideo RC840T-240 (22 A resistive)
Fahrenheat FUH542,50010.4Within rating
Fahrenheat FUH543,33213.9Within rating
Fahrenheat FUH544,16517.4Within rating
Fahrenheat FUH545,00020.9Within rating, 1.1 A to spare
Fahrenheat FUH7246,25026.0Over rating
Fahrenheat FUH7247,50031.3Over rating
Fahrenheat FUH1024T10,00041.7 (single phase)Over rating
King KB2407 ECO2S+7,50031.2No relay needed: 24 V terminals

The relay column uses Resideo's RC840T, sold under the Aube name. It is made "to control a line voltage resistive load from a low voltage thermostat." Resideo rates it 22 A resistive at 120, 208 and 240 V. At 240 V that is 5,280 W. Anything bigger needs a contactor with a higher resistive rating.

Switch the elements, never the fan. Marley's accessory manual for its F series ceiling heaters is blunt. The controls it covers, including the FR2-24V relay kit, "must be wired to cycle the heating element circuit only." It goes on: "The motor circuit is controlled by the fan delay and must remain energized at all times unless heater circuit is disconnected." The warning is there "To prevent permanent damage to heater or a possible fire hazard." King's manual says the same thing in its own words: "Power must land at heater uninterrupted by switches or thermostat due to thermal fan delay."

That rules out the obvious shortcut of a relay or a line-voltage thermostat in the heater's supply cable. Cut the whole supply and the fan stops with the elements still hot. The relay belongs where the heater maker's manual puts a remote thermostat or relay kit. Marley's FR2-24V kit mounts on the heater's own fan panel for that reason.

Power the thermostat separately. The RC840T has a built-in 24 V transformer and works with "3-wire (R,C,W) thermostats." But Resideo rates that transformer at "24 VAC / 1.2 VA." Google lists the Nest Learning Thermostat (4th gen) at 4 VA at startup and 2 VA in standby. ecobee lists the Smart Thermostat Enhanced at 1.6 W idle and 2 W peak. Both need more than 1.2 VA, so neither should run off the relay's transformer.

The answer is a separate 24 V transformer for the thermostat. How it connects depends on the thermostat:

The same two layouts appear in the pellet stove page and the millivolt fireplace page. Add the coil's VA to the thermostat's when you size the transformer, using the method in video doorbell transformer sizing.

Why not a line-voltage smart thermostat?#

Mysa and Sinopé make Wi-Fi thermostats that switch 240 V directly. Their limits are on the baseboard page: 3,000 W at 240 V for Sinopé's standard models and 3,800 to 4,000 W for the largest. A 5,000 W FUH54 is over all of them.

Sinopé's own answer for bigger loads is its low-voltage TH1400WF, listed as compatible with "heating with mechanical relays." On that product page Sinopé told a buyer that a power relay may be required for a load over 4,000 W. That is Route 2 with a different thermostat.

Size is only half the problem. A line-voltage thermostat sits in the heater's supply, and on a unit heater that is the cable King and Marley say must stay live for the fan.

How low each thermostat goes#

A garage is often kept just above freezing, not at room temperature. Here is how low each control will let you set the heat:

ControlLowest normal heat setpointLower optionRated to operate in
Nest Learning Thermostat (4th gen)50°FEco heating down to 40°F32°F to 104°F
ecobee Smart Thermostat Enhanced45°FNone stated14°F to 122°F
King ECO2S+ built-in control40°FNone statedNot stated
Fahrenheat FUH built-in thermostat45°FNone statedNot stated

So none of the four holds 35°F. The Nest's Eco setting can reach 40°F. Google also has Safety Temperatures, which turn the heat on "even if the thermostat is set to Off." The ecobee's floor is 45°F. The Nest's own operating range starts at 32°F, which is one more reason to keep the garage above freezing or mount the thermostat on a warm wall.

Worked through: a 5,000 W FUH54 and a Nest#

Here is one case, walked through the published figures. Take a Fahrenheat FUH54 wired for 5,000 W at 240 V, hung in a two-car garage. The owner wants a Nest Learning Thermostat (4th gen) on the wall and the garage held at 50°F.

The amps. Fahrenheat lists 20.9 A for this model at 5,000 W. A Resideo RC840T-240 is rated 22 A resistive at 240 V. That covers it, with 1.1 A to spare.

The circuit it breaks. The relay replaces the built-in thermostat's job of switching the elements. The fan delay keeps its own power. The heater's supply stays connected at all times, as Marley and King require. Where exactly the relay connects comes from Fahrenheat's installation manual. The spec sheet read here does not show a remote control diagram.

The thermostat's power. The RC840T's transformer is rated 1.2 VA, and the Nest needs 4 VA at startup. So a separate 24 V transformer goes on the Nest's Rc and C. The relay's R and W go on Rh and W1. Nothing joins Rh to Rc.

The setpoint. 50°F is the Nest's lowest normal heat setpoint, so it works here. On a week away, Eco can drop it to 40°F.

The outcome. When the garage falls below 50°F, the Nest closes Rh to W1. The relay closes and the elements heat. The fan delay starts the fan once the elements are warm. When the call ends, the relay opens, and the fan runs on until the elements cool.

Now swap in the FUH724 at 7,500 W. Fahrenheat lists 31.3 A, which is 9.3 A over the RC840T's rating. The plan needs a contactor rated above 31.3 A, and everything else stays the same. Swap in King's 7.5 kW KB2407 instead, and the relay goes away. The Nest wires straight to the heater's R, C, W1, W2 and G terminals.

Which route, by heater#

Each row restates a ruling from the sections above.

Your heaterRouteWhat decides it
King KB ECO2S+ or PlatinumX, any sizeWire the Nest or ecobee to the heater's 24 V terminalsKing lists R, C, W1, W2 and G and names both brands
Marley F series ceiling heaterMarley's FR2-24V relay kit, cycling the elements onlyMarley's warning that the motor circuit stays energized
Fahrenheat FUH54, up to 5,000 WRelay rated above the heater's amps, such as the RC840T-240 at 22 A20.9 A at 5,000 W
Fahrenheat FUH724 at 6,250 or 7,500 WContactor rated above 26.0 or 31.3 AOver the RC840T's 22 A
Any unit heater, with a line-voltage smart thermostat in the supplyNot this routeCuts the fan, and the largest models stop at 4,000 W

The rule behind the table: the smart thermostat switches 24 V only. Something rated for the heater's amps switches the elements, and the fan keeps its power.

Running it day to day#

Once the heater is on a smart thermostat, schedules and remote changes become easy. A heater kept for freeze protection matters most when no one is home, so check what still works when the internet goes down. Whether your schedule runs on the thermostat or in the cloud is covered in local versus cloud control. Pipes in a cold garage may also need heat tape, which has its own plug limits in pipe heat tape on a smart plug.

Where this page stops#

This page rests on heater documents from Fahrenheat, Marley and King, Resideo's relay guide, and spec sheets from Google, ecobee and Sinopé, read in November 2026. Some were read from retailer copies, as the source list notes. Fahrenheat's spec sheet does not show where a remote relay connects inside the FUH, so that wiring comes from its installation manual, which was not read. Neither Google nor ecobee publishes a relay layout for an electric unit heater, and nothing read says whether they support one. The amp sums above size the relay. They do not size the circuit, which the electrical code sizes separately, as the 240 V water heater page explains for another heater. Resideo's diagrams carry the note "YOU MUST PROVIDE AN OVERLOAD PROTECTION AND DISCONNECT AS REQUIRED." A relay does not replace the heater's disconnect, and 240 V work is a job for an electrician in many places. Renters should read a smart home for renters first. Three-phase heaters, gas unit heaters and 120 V plug-in heaters are out of scope. Plug-in heaters are covered in space heaters on a smart plug. The wider wiring picture is in smart thermostats and the C wire.

Can a Nest thermostat control a 240V garage heater?

Yes, but only through 24 V. If the heater has 24 V thermostat terminals, as King's ECO2S+ does, wire the Nest to them. If not, the Nest drives a relay rated above the heater's amps, and the relay switches the elements. The Nest never carries the 240 V current.

What size relay do I need for a garage heater?

One rated above the heater's amps at its voltage, for a resistive load. Amps are watts divided by volts. A 5,000 W heater at 240 V draws 20.9 A, which fits Resideo's RC840T at 22 A. A 7,500 W heater draws 31.3 A and needs a larger contactor.

Can I put a Mysa or Sinopé thermostat on a garage unit heater?

Usually not. The largest line-voltage smart thermostats stop at 3,800 to 4,000 W at 240 V. They also sit in the heater's supply, which cuts the fan, and King and Marley say the fan circuit must stay powered.

Can I set a Nest or ecobee to 40°F for a garage?

A Nest's lowest normal heat setpoint is 50°F, but its Eco setting goes down to 40°F. The ecobee Smart Thermostat Enhanced goes down to 45°F. Neither holds 35°F as a normal setpoint.

Why must the garage heater fan stay powered?

The fan delay runs the fan after the elements switch off, to carry their heat away. Marley warns that cutting the motor circuit risks "permanent damage to heater or a possible fire hazard," and King says power must reach the heater uninterrupted.

Does the relay's built-in transformer power a smart thermostat?

Not on the RC840T. Resideo rates its transformer at 1.2 VA. A Nest Learning Thermostat (4th gen) needs 4 VA at startup and an ecobee Enhanced peaks at 2 W, so give the thermostat its own 24 V transformer.

Primary sources

Specification and vendor documentation we checked while writing this page. Where a claim depends on firmware behaviour rather than a published spec, the page says so inline.